Design No. U913

Bearing Wall Rating - 2 HR.
Nonbearing Wall Rating - 2 HR.

U913

  1. Concrete Blocks* - Various designs Classificaon D-2 (2 hr).
  2. Mortar - Blocks laid in full bed of mortar, nom. 3/8 in. thick, of not less than 2-1/4 and not more than 3-1/2 parts of clean sharp sand to 1 part Portland cement (proportioned by volume) and not more than 50 percent hydrated lime (by cement volume). Vertical joints staggered.
  3. Foamed Plastic* - Min 1 in. thick, density of 1 pfc max, polystyrene foamed plastic insulation boards, suppiled in 2 by 4 ft sheets. Positioned horizontally and staggered 24 in. OC vertically, and attached to the concrete blocks (Item 1) with adhesive/base coat (Item 5) applied at a rate of 1-1/2 gal per 100 sq. ft.
         Associated Foam Manufacturers - Type WSG
  4. Non-Metallic Fabric Mesh (not shown) - Glass fiber fabric mesh, weighing approximately 2.5 oz/sq yd, positioned vertically over the foamed plastic (Item 3) and secured at the top with 16 gauge 3/8 in. long staples randomly spaced.
  5. Wall and Partition Facings and Accessories - Coating System - The base coat is trowel-applied over glass fiber fabric mesh (Item 4) at a rate of 2 gal per 100 sq ft. The textured wall finish is then applied over the base coat at a rate of 2-1/2 gal per 100 sq. ft.
         Gaco Western Inc. - Types A-5200, -5207, -5214, -5216, -5218, -5250.

*Bearing the UL Classification Marking